The DB series consists of the new DB1000, which inherits the functions of the long-selling model, the old DB1000, and the DB2000, which has even more advanced functions. With an accuracy of 0.1%, sampling cycle of 0.1 seconds, and a size of 96 x 96 mm, this is an all-in-one type that covers almost all of the general functions required for a temperature controller.
PV and SV display in large, easy-to-read 5-digit LEDs. The lower display shows the output status in analog display digital display at the same time, allowing you to check PV/SV/MV at a glance. We also offer models that can be switched between the conventional control method and our proprietary Z control method, which is an evolved algorithm of the conventional PID method. Z control is effective in suppressing over and shortening settling time in heating control, etc. (Z control is Japan Only)
Regulation Mode (Output 1) | Standard Type |
---|---|
On-off pulse type | DB1010B000-G0A |
On-off servo type (Standard load specifications) |
DB1020B000-G0A |
Current Output Type | DB1030B000-G0A |
SSR drive pulse type | DB1050B000-G0A |
Voltage Output Type | DB1060B000-G0A |
On-off servo type (Micro load specifications) |
DB1080B000-G0A |
Input Signal | Thermocouple: B, R, S, K, E, J, T, etc. DC voltage: ±10mV, ±20mV, ±50mV, ±100mV, ±5V, ±10V DC current: 20mA resistance thermometer: Pt100, JPt100, etc. |
||
---|---|---|---|
Accuracy ratings | ±0.1% of input span ±1 digit | ||
Reference junction compensation accuracy | K, E, J, T, N, Platinel II: ±0.5°C or ±20μV equivalent, whichever is greater Others: ±1.0°C or ±40μV equivalent, whichever is greater |
||
Sampling Period | 約0.1秒 | ||
Burnout | higher limit burnout is standard only for thermocouples, DC voltage (±50mV or less), and resistance thermometer (3-wire type) At the time burnout, the output value of the first output side can be selectable, the output value of the second output side is 0%, and higher alarm is ON (at the time higher limit burnout) |
||
Display element | First display LED Second display LCD (with back-lit illumination display) 108 x 24 dots |
||
Rated power supply voltage | General specifications 100 to 240V AC 24V power supply specifications 24VAC/24VDC |
||
Weight | No option Approx. 450g With option Approx. 580g |
||
Output models | current output type, on-off pulse type, voltage output type, SSR drive pulse type, on-off servo type | ||
Adjustment setting | 8 types of PID P: 0 to 999.9% (0 for 2-position operation) I: 0 to 9999 seconds (0: no integral action) D: 0 to 9999 seconds |
||
Anti reset Windup |
higher limit: 0.0 to 100.0% lower limit...-100.0 to 0.0% |
||
On-off pulse type | Output signal: | On-off pulse conduction signal | |
contact Capacity: | resistance load 100~240VAC 30VDC, 5A or less inductive load 100~240VAC 30VDC, 2.5A or less Minimum load 5VDC 10mA or more |
||
On-off servo type | Output signal: | on-off servo conduction signal | |
contact Capacity: | resistance load 100~240VAC 30VDC, 5A or less inductive load 100~240VAC 30VDC, 2.5A or less Minimum load 5VDC 10mA or more |
||
Current Output Type | Output signal: 4 to 20mA DC load resistance: 750Ω or less |
||
SSR drive Pulse Shape |
Output signal: | On-off pulse voltage signal | |
Output voltage: | ON voltage 12VDC±20% OFF voltage 0.8VDC or less |
||
Voltage Output Type | Output signal: 0 to 10V Output impedance: Approx. 10 Ω load resistance: 50kΩ or more |
||
Alarm points | 4 points |
If you register as a CHINO Web member, you will be able to view the product's instruction manual.
If you wish, we will send you the latest information on CHINO products via email.
You must be a login to download.