The LH100/LH110 piping temperature controller is a regulator with a built-in SSR in a slim body.
It uses a push-in connector that significantly reduces installation time. It also comes standard with RS-485 communication, digital input, and event output, providing cost-effective temperature control. The LH700 EtherCAT converter for LH is a converter that enables EtherCAT compatibility when combined with the LH100/LH110. The LH700 has passed conformance testing at an official certification test center recognized by ETG (EtherCAT Technology Group), an international organization that promotes EtherCAT technology development.
Product name | Models | Specifications |
---|---|---|
Pipe Temperature Controller | LH100-NN | No setting display |
LH101-NN | No setting display, moisture-proofing (internal printed circuit board) | |
LH110-NN | With setting display | |
LH111-NN | With setting display, moisture-proofing (internal printed circuit board) | |
EtherCAT converter for LH | LH700-NN | EtherCAT slave device for LH100/LH110 |
LH701-NN | EtherCAT slave device for LH100/LH110, moisture-proofing treatment (internal printed circuit board) |
Model | LH100 | LH110 |
---|---|---|
Input Signal | Thermocouples: K, J resistance thermometer: Pt100 |
|
Measurement range | 0 to 800°C (common) | |
Accuracy ratings | ±0.2% of measurement range FS ±1digit | |
Reference junction compensation accuracy | ±2℃ | |
Input capture cycle | 約0.1秒 |
Model | LH100 | LH110 |
---|---|---|
Output Type | Triac output (zero cross) | |
Allowable load current | 7A | |
Control Period | 約0.1秒 | |
Pulse Period | 0.5 to 180 seconds |
Model | LH100 | LH110 | ||
---|---|---|---|---|
Setting display (Japan Only) | None | Available | ||
Power supply voltage | 100-240V AC | |||
Power frequency | 50/60Hz | |||
Power consumption | When no load is connected | Maximum 4VA (100V) / Maximum 6VA (240V) | Maximum 5VA (100V) / Maximum 7VA (240V) | |
When load is connected | Maximum 704VA (100V) / Maximum 1686VA (240V) | Maximum 705VA (100V) / Maximum 1687VA (240V) | ||
Operating temperature/humidity range | Temperature: -10 to 60°C Humidity: 20 to 90% RH (no dew condensation) |
Model | LH100 | LH110 |
---|---|---|
Number of input points | 1点 | |
Input Signal | Non-voltage contact or open collector | |
function | AUTO/MANUAL, RUN/READY, built-in relay ON/OFF |
Model | LH100 | LH110 |
---|---|---|
Number of Outputs | 1点 | |
Output Capacity | 24VDC 50mA | |
function | Absolute value alarm, deviation alarm, absolute value deviation alarm, control loop abnormality alarm, FAIL alarm |
device Profiles | Semiconductor Device Profile |
---|---|
bit rate | 100Mbps |
protocol | CoE, FoE |
Synchronous Mode | FreeRUN, SM, DC |
Communication Cycle | 5 to 100 ms |
transmission distance | 100m or less (between nodes) |
Power supply voltage | 100-240V AC |
---|---|
Power frequency | 50/60Hz |
Power consumption | 6VA(100V) /Max. 8VA(240V) |
Operating temperature/humidity range | Temperature: -10 to 60°C Humidity: 20 to 90% RH (no dew condensation) |
We offer products related to "temperature measurement and control" in the semiconductor front-end process, as well as system proposals that combine these products.
We will introduce solutions related to temperature measurement and control in process of "ingot pulling," "wafer polishing/oxidation," "etching," and "film formation," as well as "superconductivity," "artificial diamond," and "thermography that can withstand temperatures up to 150°C."
Controller with built-in SSR suitable for piping temperature control
The LH100/LH110 piping temperature controllers come standard with functions that are highly necessary in various control situations, such as a controller function, SSR, RS-485 communication, digital input, and event output. This makes it easy to build a control system. The LH700 is also available as an EtherCAT slave device.
If you register as a CHINO Web member, you will be able to view the product's instruction manual.
If you wish, we will send you the latest information on CHINO products via email.