Intrinsically safe explosion proof thermocouple SC, NC (Japan Stadnards)

Sheathed and solid-pack temperature sensors, when combined with a Zener barrier or insulation barrier, have passed the intrinsically safe explosion proof equipment inspection by the Technology Association of Industrial Safety (a type inspection agency designate the Ministry of Health, Labor and Welfare).

■ Zener Barrier
· DIN rail mounting and intrinsic safety ground (earthing) are possible at the same time.

■ insulation barrier
・No installation work required. Excellent noise resistance because no installation is required.

configuration of a sensor, a Zener barrier, and an insulation barrier

Specifications

Intrinsically safe explosion proof proof thermocouple

Sensors Models SC/NC series
Wire and element R, N, K, E, J, T, etc.
Protection tube dimensions Outer diameter φ1.0~22mm
Length: 50 to 50,000 mm
explosion proof specifications models name IS11
explosion proof structure types Intrinsically safe explosion proof proof structure (IA)
Explosion class and ignition level of the target gas or vapor IICT5
Permissible voltage of intrinsically safe circuit 10V
Permissible current of intrinsically safe circuit 400mA
Type inspection approval number No. TC19165

Zener barrier (for resistance thermometer)

Combination Barrier Models MTL7760ac
Non-intrinsically safe circuit allowable voltage 250V AC 50/60Hz
250V DC
Voltage and current used 6V AC 50mA
terminal resistance 75Ω (max.)
Type inspection approval number No. TC16619

insulation barrier (for resistance thermometer)

Combination Barrier Models MTL5575
Non-intrinsically safe circuit allowable voltage 250V AC 50/60Hz
250V DC
Output Signal 4 to 20mA
Power supply 20-35V DC
Maximum current consumption 35mA (at 24V DC)
Type inspection approval number No. TC20267
*Please refer to the catalog for other specifications.

Download Documents & Softwares

Catalog

Specification Sheet (PS Sheet)

  • Intrinsically safe explosion proof insulation barrier (for thermocouples/ resistance thermometer)
    ファイルサイズ1MB
    Document No.
    PE-70-2
  • Intrinsically safe explosion proof Zener barrier (for thermocouples/ resistance thermometer)
    ファイルサイズ1MB
    Document No.
    PE-58-3

CAD Data

*Downloading materials is a members-only service.
*If you wish to download, please login as a member and click "Download."

Instruction Manual

*Downloading materials is a members-only service.
*If you wish to download, please login as a member and click "Download."

Softwares

Application Examples

RelatedInfo

movie

If you have any problems with temperature control,
 please feel free to contact us.

Membership
CHINO Web Membership Information

If you register as a CHINO Web member, you will be able to view the product's instruction manual.
If you wish, we will send you the latest information on CHINO products via email.

You must be a login to download.