Frequently Asked Questions (FAQ)
What precautions should be taken when using a transformer as load?
To prevent biased magnetism in the iron core, we recommend that the magnetic flux density of the transformer be 1.2T (tesla) or less.
In addition, to reduce the effect when there is no load, please install a bleeder resistance that flows 0.5A or more on the primary side of the transformer.
Please ensure that the bleeder resistance has a sufficient rated power (three times or more is recommended) and that this is reflected in the thermal design of the panel.