Frequently Asked Questions (FAQ)

I am using the communication service. After updating from the old KP to the new KP, I can no longer communicate. Why?
The old KP only had a "PRIVATE" communication protocol type, but the new KP has added "MODEBUS RTU" and "MODBUS ASCII", and the default value is "MODBUS RTU". Set the communication protocol type of the new KP to "PRIVATE" and set the communication speed to the same as other devices that are communicating.

If you have any problems with temperature control,
 please feel free to contact us.